Water Cooled Ulmate Chiller Soluon Model UCW/H 30, 50, 70, 85 Installaon, Operaon & Maintenance Manual
www.climacoolcorp.com8Mounting Rail and Vibration Isolation ClimaCool recommends locking down the chiller to a concrete base or to three (3) 4” base
9www.climacoolcorp.comRecommended Service ClearancesNotes: 1. Allow 36" clearance for electrical panels and 30" clearance for rear service
www.climacoolcorp.com10Water PipingAs with any water system, it is important that the system be clean. The pipe work installer must remove weld scale,
11www.climacoolcorp.comClimaCool oers two types of water header bypass kits, direct return (Figure 6) and reverse return (Figure 7) as shown on page
www.climacoolcorp.com12Water Piping CongurationsNotes: 1. Figures 9 and 10 are required piping for proper water regulation and distribution through
13www.climacoolcorp.comHydronic Refrigeration The ClimaCool Modular Chiller - Hydronic ConfigurationFigure 1 - Condenser Hydronic CircuitFigure 2 - Ch
www.climacoolcorp.com14Filling the Water SystemIt is imperative that the water systems are free from debris prior to initial operation. See Water Tre
15www.climacoolcorp.comWater TreatmentWater quality is of the utmost importance for the proper care and maintenance of the modular chiller system. Pro
www.climacoolcorp.com16Chilled Water TemperatureModules are designed for a leaving water temperature range from 40°F to 62°F. All cataloged modules ca
17www.climacoolcorp.comCondenser and Evaporator Water Pressure Drop Charts - 030, 050, 070, 085100Condenser Water Pressure Drop30, 50, 70 & 85-Ton
Table of ContentsIntroduction ...1Pre-Installation ...2Unit Installation ...
www.climacoolcorp.com18Glycol Performance Adjustment Factors ChartsNote: Correction factors shown above are to be applied to Std. Product Data @ ARI
19www.climacoolcorp.comGlycol Performance Adjustment Factors ChartsGlycol Solution Freezing Point
www.climacoolcorp.com20Electrical ConnectionThe power for all modules is taken from a suitable circuit breaker/fused disconnect power supply within th
21www.climacoolcorp.comVoltage/Phase Monitor Wiring
www.climacoolcorp.com22Pre-StartupAll startups must be performed by ClimaCool factory trained personnel. Prior to chiller startup, there are certain e
23www.climacoolcorp.com PreStartUp R-410A WaterCool 11.02.12 Project Name: _________________________________________________Date:__________
www.climacoolcorp.com24StartupAll startups must be performed by ClimaCool factory trained personnel.1. Review all items are complete from the Pre-Sta
25www.climacoolcorp.comthe FN 7, or the service menu). Bump the compressor only for 1-2 seconds to ensure the correct rotation of the scroll compresso
www.climacoolcorp.com26RunCompressorfor 5 MinutesIs Superheatin Range?YesNoIs Subcoolingin Range?YesNoIs Superheat Low or High?HighLowTurn TXVAdjustme
27www.climacoolcorp.comPageProject Name: Contractor Name:Address: Address:City/State City/StateStart-up Date: Phone No.:Model No.: Model No.:Serial No
1www.climacoolcorp.comIntroductionGeneral DescriptionClimaCool’s dedication to energy and environmental leadership led to the Ultimate Chiller Solutio
www.climacoolcorp.com28Project Name: Software Version:General System Settings FN 2 COOLING PID FN 8Chiller Control Type PID IntervalControl Source Use
29www.climacoolcorp.comMod Water & Air Temp Limits FN6 Channel 8 & 11 Setup FN8Mod Evap Water Out Low Limit Use Channel #8 as diff pressure
www.climacoolcorp.com30• Check water ow rates and pressure drops across evaporator and condenser heat exchangers.• Properly document all data taken
31www.climacoolcorp.comHeat Exchangers Draining When performing standard maintenance procedures such as ushing a heat exchanger, it will be neces
www.climacoolcorp.com32Cleaning ArrangementFigure 14 - City Water Cleaning ArrangementNotes:1. When backwashing, be sure to ush in opposite directio
33www.climacoolcorp.comOperational Limitations Water Flow DataUCW/H 030 UCW/H 050 UCW/H 070 UCW/H 085Minimum Evaporator Water Flow (gpm)40 65 85 100Ma
www.climacoolcorp.com34Compressor Information Model UCW/H uses scroll compressors which are highly ecient and extremely reliable. The information
35www.climacoolcorp.comRefrigeration Circuit DiagramSIZEClimaCool Corp.CCE-08001-2.VSDDWG NOCCE-08001-2.VSDREVSHEET 1 OF 1TITLEREFRIGERATION CIRCUIT D
www.climacoolcorp.com36Refrigeration Circuit DiagramSIZEClimaCool Corp.CCE-09001-2.VSDDWG NOCCE-09001-2.VSDREVSHEET 1 OF 1TITLEREFRIGERATION CIRCUIT D
37www.climacoolcorp.comConforming to local and national codes is the responsibility of the service technician or installing contractor. The service te
www.climacoolcorp.com2Pre-InstallationInspectionUpon receipt of equipment, carefully check the shipment against the bill of lading and inspect each ch
www.climacoolcorp.com38Options and AccessoriesMotorized or Manual Water Isolation Valves and Flush Ports Factory installed water isolation valves and
39www.climacoolcorp.comStainless Steel Strainer OptionFigure 16Safety Considerations Prior to installation, this manual must be read carefully and all
www.climacoolcorp.com40Strainer Operation Periodically, it will be necessary to ush out the debris that is collected and settles to the bottom of th
41www.climacoolcorp.comWhat is Water Hammer?Water hammer is a phenomenon that can occur in uid systems with long pipes. Water hammer is a rapid chang
www.climacoolcorp.com42Operation Instructions Flush valve line must be piped to atmospheric pressure such as an open oor drain. The ush line should
43www.climacoolcorp.comWhen the dierential set point is reached both the audible and visual alarms will be triggered and will remain engaged until bo
www.climacoolcorp.com44“Y” StrainerBefore installing the “Y” strainer, be sure its pressure rating is correct for the system. If the end connections a
45www.climacoolcorp.comElectrical Data UCWRated Min.Cir. MaxFuse Rec. Discon. Rated Min.Cir. Locked MaxFuse Rec.Load Amps Size Fuse Switch Load Amp
www.climacoolcorp.com46Electrical Data UCHRated Min.Cir. MaxFuse Rec. Discon. Rated Min.Cir. Locked MaxFuse Rec.Load Amps Size Fuse Switch Load Amp
47www.climacoolcorp.comPower Distribution DrawingPower Distribution DrawingNotes:1. Breaker panel represents eld power supply and is to be installed
3www.climacoolcorp.comUnit InstallationUnit PlacementClimaCool modular chillers must be installed in a conditioned and dehumidied space. The minimum
www.climacoolcorp.com48Wiring Diagrams - 030, 050, 070
49www.climacoolcorp.comWiring Diagrams - 030, 050, 070
www.climacoolcorp.com50Wiring Diagrams - 030, 050, 070 Heat Pump
51www.climacoolcorp.comWiring Diagrams - 030, 050, 070 Heat Pump
www.climacoolcorp.com52Wiring Diagrams - 085
53www.climacoolcorp.comWiring Diagrams - 085
www.climacoolcorp.com54Wiring Diagrams - 085 Heat Pump
55www.climacoolcorp.comWiring Diagrams - 085 Heat Pump
www.climacoolcorp.com56Wiring Diagrams
57www.climacoolcorp.comWiring Diagrams
www.climacoolcorp.com4RejectionMeansW=Water ModelConfigurationH=HighTemperature S=Standard
www.climacoolcorp.com58Troubleshooting GuideWARNING!The troubleshooting guidelines recommended in this section could result in exposure to electrical
59www.climacoolcorp.comTroubleshooting Guide Compressor Cycle On High Pressure Control Possible Cause Remedy Main condenser water valve closed or res
www.climacoolcorp.com60Warranty Certicateforms\ccool\standard forms\word files\warranty compressor certificate 04-12 WARRANTY DISCLAIMER It is e
ClimaCool works continually to improve its products. As a result, the design and specications of each product at the time for order may be changed wi
5www.climacoolcorp.comPhysical Data Model UCW/H Module and Compressor30 50 70 85Capacity (tons) ¹31.7 51.5 67.2 82.8kW/Ton0.738 0.746 0.744 0.740Full-
www.climacoolcorp.com6Dimensional Data and DrawingsP5Chiller Type Header A Header BUCW Chilled Water Outlet Chilled Water InletUCH Heat Recovery Chill
7www.climacoolcorp.comRigging and Lifting ProceduresRiggingEach module should be lifted using lift straps threaded through the steel base cutouts and